ezns-t100 network sensor building automation controller

The eZNS-T100 network sensor offers building occupants an intuitive touch-interface to adjust individual comfort levels while tailoring to the needs of their specific market. Featuring a standard temperature sensor with humidity, CO2 and motion options, the eZNS also offers a choice of backlit colors to provide additional user feedback and esthetic appeal.


The eZNS sensor’s NFC technology allows installers to use NFC-enabled mobile devices to configure the eZNS and enable enteliWEB integration.


The eZNS is suitable for a wide range of sensing applications, from basic temperature monitoring, to indoor air quality and occupancy sensing. A customizable interface allows for intuitive user interaction.

An available external input allows for additional zone monitoring such as window or door contact, temperature averaging or other dry contact sensor information.

When paired with an application controller, the eZNS supports advanced control strategies such as demand control ventilation, energy savings based on occupancy and optimal user comfort.


  • RGB back-light allows choice of colors to indicate conditions, alarms and night mode
  • Large easy-to-read LCD screen. Onscreen visual feedback on button selection.
  • Capacitive touch zones allow custom button sizes
  • Multiple button layout options. Simple one-touch buttons, or two-touch buttons for added functionality
  • Slider to quickly adjust setpoint or tap for precise changes
  • Fully programmable in GCL+
  • USB Service port, software enabled or disabled. Service tool not required.
  • Smartphone and tablet integration and setup using NFC technology
  • Recessed mount for minimal profile or surface mount backplate options
  • Fits most electrical boxes worldwide
  • 2-piece design with tamper set screw lock


LCD (Optional) 

2-line custom segmented display with icons 


2 rows of 4 capacitive touch zones, allowing up to 8 individual buttons or combined to form larger buttons 

Backlight (Optional)

Optional RGB LED backlight for multicolor LCD and button illumination 


Digital Temperature Sensor 

+/- 0.2° C (+/- 0.36°F) 

Humidity Sensor (Optional) 

Accuracy +/- 3% 

CO2 Sensor (Optional) 

Dual Beam, Self Calibrating NDIR Detection 

Range: 0-2000 ppm 

Accuracy @ 77°F (25°C): 

± (50ppm + 2% of value) 

Temperature Dependence: 

2ppm/°C (1 ppm/ °F) typical 

Pressure Dependence: 

0.13% of reading per mm Hg 

Stability: 20 ppm/year (typical) 

Occupancy Sensor (Optional) 

Passive infrared motion (PIR) sensor 

Range: 5m (16.4 ft.) 

Coverage: 100° Horizontal 


1 10kΩ input (16 bit A/D)


32-bit processor Internal A/D, Flash and RAM


RS-485 port Delta LINKnet (up to 76800 bps)

USB Service Port 

Used as virtual Com port to connect the BACnet® network to a workstation

Near Field Communication (NFC) Passive 2-way short range


Screw-type terminal connectors

Wiring Class 

Class 2 / SELV


24 V AC/DC 

2 VA no backlight 

4 VA with backlight 

6 VA with backlight and CO2 sensor


32° to 131°F (0° to 55°C) 

10 - 90% RH (non-condensing)


With R (non-CO2 ) and SM backplate: 

5.3 x 3.6 x 0.9 in. (13.3 x 9.3 x 2.3 cm) 

With R (CO2 ) backplate: 

5.3 x 3.6 x 1.7 in. (13.3 x 9.3 x 4.3 cm)


Mounted Surface Profile 

Recessed (both R backplates): 0.75 in. (1.9 cm) 

Surface Mount (SM backplate): 

0.9 in. (2.3 cm) 

IP Rating 

IP20 Compliance 


FCC Class B


UL 916