DVC 322E VAV Controller for Building Automation

The DVC-V322 is a fully programmable, Native BACnet™ Advanced Application Controller that communicates on an RS-485 LAN using the BACnet MS/TP protocol. This controller is specifically designed for VAV applications and supports the Delta BACstat and LINKnet I/O. The damper actuator assembly is available with or without position feedback. Additional inputs and outputs can be configured as required.


The DVC-V322 is an application-specific controller for VAV and includes an actuator and true differential pressure sensor with integrated housing. The fully programmable DVC-V322 allows GCL+ programs and BACnet objects to be tailored to any VAV application.


  • Native BACnet firmware
  • BACnet MS/TP communications
  • Supports 4 BACstat network sensors on LINKnet for room sensing and control or 2 Delta Field Modules on LINKnet for I/O expansion
  • Integrated housing with damper assembly for easy and cost effective installation
  • Reliable industry standard actuator (with optional position feedback)
  • True differential pressure sensor
  • Fully programmable in GCL+
  • Application database can be flash loaded over the network
  • Controller firmware can be flash loaded over the network
  • Supports Modbus capability via flash loading in the field
  • Supports flash loading Modbus upgrades via hardware key
  • Derived Network Addressing (DNA) for simple integration into a standard network architecture
  • Service port

BACnet Device Profile

BACnet Advanced Application Controller


Inputs - External

3 Universal inputs - 10 bit (supporting 0-5v, 0-10v, 10kΩ, 4-20mA)

Inputs - Internal

1 Actuator position feedback input (optional)

1 Air flow input

Flow Sensor, true differential pressure - 0-1”

H2O (0-248.8 Pa)

Outputs - External

2 Binary triac outputs & 2 analog outputs

(0-10 VDC)

LED status indication of each output

Outputs - Internal

2 Binary outputs for damper open and close


44 in-lbs. (nominal torque)

Less than 35db (A) noise level


35 in-lbs. (nominal torque)

Less than 35db (A) noise level

Differential Pressure

0 to 1” H2O (0 - 248.8 Pa)


Flow sensor tubing must be 5/32” inside diameter

Device Addressing

Set via DIP switch and jumpers, or software setup


32-bit processor

1 MB (8 megabit) Flash memory

127 KB SRAM memory for database

LED indication of CPU and SCAN status

Communications Ports


BACnet MS/TP @ 9600, 19200, 38400 or 76800 bps(default) (maximum of 99 devices per BACnet MS/TP segment)


Delta LINKnet @ 76800 bps (maximum 4 devices on LINKnet, with no more than 2 DFM devices)


Removable screw-type terminal connectors

Wiring Class

Class 2


24 VAC with LED status

15 VA (not including output loading)


32° to 131°F (0 to 55°C)

10 - 90% RH (non-condensing)


9 3/8 x 4 3/4 x 3 1/8 in. (23.9 x 12.0 x 8.0 cm) with housing

1.85 lb. (840 g) with housing and actuator





UL 916 Listed

C-UL Listed

BTL Listed

UL 864 Listed