DLC-G1212
Description: The Delta GE Lighting Controller is a Native BACnet™ Application Controller that communicates on a BACnet MS/TP RS-485 LAN. The controller is designed for lighting applications and can switch a minimum of 12 GE lighting relay outputs per controller.
The controller also supports up to 12 Delta BACstats connected on its LINKnet™ Subnetwork. Lighting strategies are written in Delta’s powerful GCL programming language, rather than residing in fixed algorithms. Both firmware and controller databases are loadable over the network.
Application: The DLC-G1212 is suitable for controlling up to 12 lighting zones, switching a maximum of 48 GE lighting relays. The controller can be mounted in various GE relay enclosures for both new and retrofit construction projects. The DLC-G1212 is fully programmable: GCL+ programs and BACnet objects can be created and or modified for specific lighting applications.
Features:
- Native BACnet firmware
- BACnet MS/TP communication
- Supports switching a maximum of 48 RR7P or RR9P GE Lighting Relays (4 parallel relays per output) per controller
- Supports a Subnet of up to 12 BACstats (DNS-14/24)
- Supports a Master Override Switch with built-in sequencing
- Fully programmable in GCL+
- Application database can be loaded over the network
- Controller firmware can be flash loaded over the network
- Supports Modbus capability via flash loading in the field
- Supports flash loading Modbus upgrades via hardware key
- Easy-to-mount housing
- External binary inputs for motion detectors
Accessories:
- 475000—475032—Relay Capacity GE Lighting Panels: 12, 24 and 48 (Delta Peripherals Catalog)
- 475100 RR9P—Isolated pilot contact 5-wire relay with 5-pin connector
- 475101 RR7P—Standard 3-wire relay with 5-pin connector
Ordering:
Order the DLC-G1212 according to the following product numbers:
- DLC-G1212
- DLC-G1212-V2 (V2 Micro Firmware*)
*Note: Not all features described in this document are available when this option is selected.
BACnet Device Profile
BACnet Advanced Application Controller (B-AAC)
Inputs
12 external binary inputs with LED status indication
12 internal inputs for relay status built into relay connector
Outputs
12 GE lighting outputs
RR7P 3-wire relays (control only, no status)
RR9P 5-wire relays (control and status, including LED indication)
Relay Switches
12 terminals for wiring local GE switches directly to relay output
Sweeper Ports
Sweeper input port master override or sweeper input port with command sequencer
Sweeper output port with LED status indication, which connects to another lighting controller’s sweeper input port to continue the sweep sequence
Communications Ports
Main LAN (NET1) with LED status indication
BACnet MS/TP @ 9600, 19200, 38400, 76800 bps (default) (maximum of 99 devices per BACnet MS/TP segment)
SubLAN (NET2) with LED status indication
Delta LINKNet @ 76800 bps (maximum 12 network sensors on LINKnet)
Technology
32-bit processor
2 MB (16 megabit) Flash memory
319 KB SRAM (database memory)
LED indication of CPU and SCAN status
Device Address
Set via DIP switch and jumpers, or software setup
Connectors
Network power inputs: removable screw-type terminal connectors
Relays: removable MTA156 AMP connectors
Wiring Class
Class 2
Power
24 VAC
50 VA (including GE relays)
Ambient
32º to 131ºF (0º to 55ºC)
10 to 90% RH (non-condensing)
Dimensions
3.94 x 11.51 x 1.81 in.
(10.0 x 29.2 x 4.6 cm) with housing
1.18 lb. (540 g) with housing
Compliance
CE
FCC Class B
Listings
UL 916 Listed
BTL Listed