DSC-R2424E
Description: The DSC-R2424E is a fully programmable, Native BACnet™ Building Controller replacement for the Intelli-Con Turbo Panel. It communicates using BACnet IP, BACnet over Ethernet or on an RS-485 LAN using the BACnet MS/TP protocol. The DSC-R2424E shares the same physical footprint, I/O expansion cards, and Zone Controller Protocol as the Intelli-Con Turbo.
Features:
- Native BACnet firmware
- V2 Intelli-Con Turbo, Intelli-Con and Intelli-Con Plus replacement controller
- Flexible input/output configuration using universal I/O points and Intelli-Con expansion cards
- Provides up to 96 I/O points
- V3 Communications: BACnet IP, BACnet over Ethernet, BACnet MS/TP or BACnet PTP
- V2 Communications: Zone Controller Protocol
- Fully programmable in GCL+
- Firmware can be flash loaded over the network
- Hand/Off/Auto switches with position feedback
- Tri-color LED’s to indicate output status
Application: The DSC-R2424E is suitable for controlling equipment such as AHUs, Boilers, Chillers and a variety of HVAC control systems.
Because of its programming capability, the DSCR2424E can be used to create or modify GCL+ programs and BACnet objects for specific applications.
Accessories:
RPT-768—Delta Network Repeater for BACnet MS/TP
TRM-768—Delta Network Terminator for BACnet MS/TP
CON-768—Delta Network Converter
Ordering: Order the DSC-R2424E according to the following product numbers:
DSC-R2424E—24 Inputs, 24 Outputs, Intelli-Con Zone Protocol, BACnet over Ethernet, BACnet MS/TP, HOA switches with feedback
- Expansion I/O
- EXP110—8 Digital Inputs
- EXP120—8 Universal Inputs
- EXP130—16 Universal Inputs
- EXP140—16 Digital Outputs
- EXP161—8 Universal Outputs
Inputs
24 Universal inputs - 10 bit (supporting 0-5V, 0-10V, 10KΩ 4-20 mA)
LED status indication per input
Outputs
24 Analog outputs (0-10V) software configured as analog or binary
LED status indication per output
Expansion I/O
3 Expansion slots (8 or 16 I/O points per slot), input or output boards available
Technology
32-bit processor
2 MB (16 megabit) Flash memory
512 KB SRAM memory
Real-time clock
SuperCap backup of clock and SRAM
Communication
Twisted-Pair Ethernet
(10-BaseT) @ 10 MB, BACnet IP, BACnet over Ethernet
V2 Zone Protocol (NET1)
Intelli-Con Zone Protocol 38400 bps (maximum 90 devices)
Main LAN (NET2)
BACnet MS/TP 9600, 19200, 38400 or 76800 bps (default) (maximum 99 devices per BACnet MS/TP segment)
Serial RS-232 BACnet PTP 9600, 19200 or 38400 bps
Device Type
Configured as either an Area, System or Subnet device
Device Addressing
Set via DIP switch or software setup
Wiring Class
Class 2
Power
24 VAC with LED status indication
50 VA
Ambient
32° to 131°F (0° to 55°C)
10 - 90% RH (non-condensing)
Dimensions
15.1 x 11.1 in. (38.4 x 28.2 x 6.4 cm)
2.20 lb. (1 kg)
Compliance
CE
FCC