DSC-633E
Description: The DSC-633E is a fully programmable, Native BACnet™ Building Controller that communicates on Twisted-Pair Ethernet 10-BaseT using BACnet IP and BACnet over Ethernet, or on an RS-485 LAN using the BACnet MS/TP protocol. The DSC-633E is designed for a wide-range of applications that have small local I/O requirements. It also supports BACstats and other Delta LINKnet devices.
Features:
- Native BACnet firmware
- BACnet IP and BACnet over Ethernet communications
- Super Capacitor for real-time clock and SRAM backup (requires no service)
- Supports 12 BACstat network sensors on LINKnet for room sensing and control or 2 Delta Field Modules on LINKnet for I/O expansion
- Actuator power terminal (24VAC) for each analog output
- Easy to mount housing
- Fully programmable in GCL+
- Application database can be flash loaded over the network
- Controller firmware can be flash loaded over the network
- Supports flash loading Modbus upgrades via hardware key
- Derived Network Addressing (DNA) for simple integration into a standard network architecture
- Service port
Application: The DSC-633E is suitable for controlling various packaged units and equipment with small I/O requirements such as Fan Coil units, Unit Ventilators, Heat Pumps, and small Boilers or Chillers.
The fully programmable DSC-633E can be tailored to specific applications by creating and modifying BACnet objects and GCL+ programs.
Accessories:
- DZNR-768—Delta Network Repeater for BACnet MS/TP
- TRM-768—Delta Network Terminator for BACnet MS/TP
- CON-768BT—Delta Network Converter
Ordering: Order the DSC-633E with the desired options according to the following product numbers:
- DSC-633E—6 inputs, 3 AO’s, 3 BO’s
BACnet Device Profile
BACnet Building Controller (B-BC)
Inputs
6 Universal inputs - 10 bit (supporting 0-5v, 0-10v, 10kΩ, 4-20mA)
Outputs
3 Binary triac outputs
3 Analog outputs (0-10v)
Jumper selection for internal or external power on binary outputs
LED status indication of each output
Technology
32-bit processor
2 MB (16 megabit) Flash memory
319 KB SRAM memory for database
LED indication of CPU and SCAN status
Real-Time Clock
Super Capacitor for 72-hour backup of real-time clock and SRAM
Device Addressing
Set via DIP switch and jumpers or software setup
Communication Ports
Twisted-Pair Ethernet
(10-BaseT) @ 10 MB, BACnet IP, BACnet over Ethernet
SubLAN (NET2)
Delta LINKnet @ 76800 bps (maximum 12 devices on LINKnet, with no more than 2 DFM devices)
Main LAN (NET1)
BACnet MS/TP @ 9600, 19200, 38400 or 76800 bps (default) (maximum of 99 devices per BACnet MS/TP segment)
Connectors
Removable screw-type terminal connectors
Wiring Class
Class 2
Power
24 VAC only
12VA, 48VA with BOs fully-loaded
Ambient
32° to 131°F (0° to 55°C)
10 - 90% RH (non-condensing)
Dimensions
8 5/8 x 4 x 1 7/8 in. (21.9 x 10.2 x 4.8 cm) with housing
0.80 lb. (360 g) with housing
Compliance
CE
FCC
Listings
C-UL Listed
UL 916 Listed
BTL Listed